Wire Sizing Guide
NEC Wire Sizing Rules
The National Electrical Code requires wire to be sized for both ampacity (current-carrying capacity) and voltage drop. The wire must satisfy both requirements — always use the larger of the two sizes.
- Ampacity: Wire must be rated to safely carry the circuit current without overheating
- Voltage drop: NEC recommends max 3% drop for branch circuits, 5% total including feeder
Common Household Circuits
| Circuit | Amps | Typical AWG |
|---|---|---|
| Lighting | 15A | 14 AWG |
| General outlets | 20A | 12 AWG |
| Dryer / AC unit | 30A | 10 AWG |
| Range / Oven | 40-50A | 6-8 AWG |
| Service entrance | 100-200A | 1-4/0 AWG |
Safety Considerations
- Always size wire for the breaker rating, not the expected load
- Derate ampacity for conduit fill, ambient temperature, and bundling
- Use THHN/THWN rated wire for most residential applications
- Longer runs almost always need upsizing for voltage drop
Copper vs Aluminum
This calculator uses copper wire values. For aluminum wire, go up 2 AWG sizes (e.g., if copper calls for 10 AWG, use 8 AWG aluminum). Aluminum requires anti-oxidant compound and rated connectors.
Disclaimer: Always consult a licensed electrician and follow local electrical codes. This calculator provides estimates for planning purposes only.
Wire Sizing, Code and Physics
The National Electrical Code 2023 (NFPA 70) Table 310.16 sets ampacity: 14 AWG copper carries 15 A, 12 AWG = 20 A, 10 AWG = 30 A, 8 AWG = 40-50 A depending on insulation type. These are the legal minimums for residential branch circuits — arc-fault and ground-fault protection are additionally required on most circuits since 2020. Undersizing conductors is the #1 finding in insurance electrical-fire investigations.
Voltage drop compounds ampacity considerations. The NEC recommends total voltage drop ≤5% (branch + feeder), and industry practice holds branch circuits to ≤3%. For a 100-foot run at 20 A and 120 V, 12 AWG drops 4.3 V (3.6%) — marginal but acceptable; the same run at 240 V drops only 1.8% because higher voltage halves current for the same power. For longer runs, 10 AWG reduces drop to 2.7 V (2.3%), usually the better choice.
EV charging has surfaced residential-wiring limits. A Level 2 charger at 40 A continuous requires a 50 A circuit (NEC 625.42 mandates 125% ampacity), which means 6 AWG copper or 4 AWG aluminum. The Edison Electric Institute estimates 70% of single-family homes lack adequate 200 A service for both an EV charger and electrification (heat pump, induction range) — upgrade costs average $2,500-$7,500 per home per the 2022 Brattle Group study.
Sources: NEC 2023 NFPA 70, Brattle Group 2022 electrification study, EEI
Methodology & Assumptions
This calculator implements standard formulas drawn from primary-source authorities. Values are point-in-time estimates; consult a licensed professional for high-stakes decisions. See the per-input definitions and source citations below.
How this works
Computations are deterministic and run client-side — no inputs leave your
browser. Formulas are derived from
standard published formulas for the calculator's domain (mortgage,
taxes, energy, conversions, etc.). When the underlying agency publishes
updated rates or thresholds we refresh defaults and update the page's
lastmod timestamp.
| Input | Default | Source / authority |
|---|---|---|
| All inputs | Domain-typical defaults | Editorial methodology, CalcMesh 2026 |