Engineering calculator
Wire Gauge Calculator, AWG Size by Current, Distance & Voltage Drop
Find the correct AWG wire gauge for your circuit based on current load, run distance, and maximum voltage drop. Covers copper and aluminum conductors.
How CalcMesh sizes wire gauge
American Wire Gauge (AWG) sizing balances current, distance and acceptable voltage drop. According to the National Electrical Code published by the National Fire Protection Association, conductor ampacity and a voltage drop under about 3% are the usual design limits.
We recommend a gauge from your current, length and voltage, but local code and conditions govern the final choice; the ampacity references we use are listed in our methodology.
Wire Sizing Guide
NEC Wire Sizing Rules
The National Electrical Code requires wire to be sized for both ampacity (current-carrying capacity) and voltage drop. The wire must satisfy both requirements, always use the larger of the two sizes.
- Ampacity: Wire must be rated to safely carry the circuit current without overheating
- Voltage drop: NEC recommends max 3% drop for branch circuits, 5% total including feeder
Common Household Circuits
| Circuit | Amps | Typical AWG |
|---|---|---|
| Lighting | 15A | 14 AWG |
| General outlets | 20A | 12 AWG |
| Dryer / AC unit | 30A | 10 AWG |
| Range / Oven | 40-50A | 6-8 AWG |
| Service entrance | 100-200A | 1-4/0 AWG |
Safety Considerations
- Always size wire for the breaker rating, not the expected load
- Derate ampacity for conduit fill, ambient temperature, and bundling
- Use THHN/THWN rated wire for most residential applications
- Longer runs almost always need upsizing for voltage drop
Copper vs Aluminum
This calculator uses copper wire values. For aluminum wire, go up 2 AWG sizes (e.g., if copper calls for 10 AWG, use 8 AWG aluminum). Aluminum requires anti-oxidant compound and rated connectors.
Disclaimer: Always consult a licensed electrician and follow local electrical codes. This calculator provides estimates for planning purposes only.
Worked example, 20 A @ 100 ft, 120 V, 3% drop
Labelled copper branch-circuit sizing check (illustrative; local NEC/AHJ governs):
- I = 20 A, one-way = 100 ft, V = 120 V, allow 3% → max drop 3.6 V.
- Ampacity alone often points to 12 AWG copper for 20 A; long run may force a larger gauge to hold drop.
- Round-trip length = 2×100 = 200 ft of conductor in the resistance budget.
- Always take the stricter of ampacity vs voltage-drop size; aluminum needs roughly two AWG sizes larger.
After you run the numbers
What to do with the results
- Satisfy both ampacity and voltage-drop, use the larger required AWG.
- Distance is one-way panel→load; resistance uses the round-trip path.
- NEC 3%/5% figures are design recommendations, your AHJ and equipment limits can be tighter.
- This page does not replace a licensed electrician’s load calculation or permit set.
Methodology & Assumptions
This circuit tool rearranges textbook electrical identities (Ohm, power, divider) on the values you enter. Component tolerances are not modelled—treat outputs as design starts.
How this circuit node runs
Ohm/power/divider tools rearrange textbook electrical identities. Real components carry tolerances the page does not invent. Published domain formulas
govern the identities; when an agency updates rates or thresholds we refresh defaults
and the page lastmod.
| Input | Default | Source / authority |
|---|---|---|
| All inputs | Domain-typical defaults | Editorial methodology, CalcMesh 2026 |